YFY Cu PVC
2XWY
November 14, 2018
A2XY UN-armoured
A2XY
November 14, 2018
Show all

2XFY

Cable Structure

    • Class : 2 Stranded Copper Wire As Per IS:8130
    • Insulated : XLPE As per IS:7098/Pt.1/1988
    • Core Identification:
      • 1 Core : Black / Red / White
      • 2 Core : Black,Red
      • 3 Core : Red,Yellow,Blue
      • 4 Core : Red,Yellow,Blue,Black
      • 5 Core : Red,Yellow,Blue,Black,Grey
      • 6 Core & above : Two adjacent cores (Counting and direction cores) in each layer,Blue & Yellow,remaining cores Grey.
    • Inner Sheath : PVC (Polyvinyl Chloride) ST2 Grade as Per IS:5831
    • Armouring : H.D.Aluminium / G.I. Strip as per IS:3975
    • Outer Sheath : PVC ST2 Grade as per IS:5831
Category:

Standard References

  • IS:7098/Pt. 1/1988

Special Features

  • Requires Less Space for Installation
  • Good Thermal Properties than PVC Variant
  • Very Good Physical Strength Than PVC Variant
  • Low Current Leakage than PVC Variant

Variants :

  • FR
  • FRLS

Application Range

  • General And Industrial Application Plant Wiring
  • Under And Ground Cables Which Require High Physical Strength

Technical Data

  • Temperature Range : -15°C to +90°C
  • Test Voltage : a.c.3 KV (rms)
  • Insulation Resistance : 1 x 1014 ohm-CM
  • Min. Bending Radius : 12 x OD (OD = Overall Diameter of Cable)
  • Short Circuit Temperature : 250°C
  • Voltage Rated : 650 / 1100 Volts

 

 

  • DIMENSIONAL TABLES,POWER CABLES – COPPER / XLPE / STRIP ARMOURED / PVC, TABLE – 1 SINGLE CORE COPPER CONDUCTOR XLPE INSULATED & PVC SHEATHED H.D.AL.STRIP  ARMOURED CABLES ACCORDING TO IS : 7098/PT. 1/1988
Core Size Stranding(Minimum No. of Strands) Nominal Thickness of Insulation(mm) Nominal Overall Diameter(mm) Approx. Weight (Kg/Km) Max DC Resistance at 20 Degree C Current Rating(amp)
SQ.MM
1 x 95.0 19 1.4 21 1150 0.193 430
1 x 120.0 37 1.5 22 1400 0.153 500
1 x 150.0 37 1.7 23 1680 0.124 577
1 x 185.0 37 1.9 25 2040 0.0991 661
1 x 240.0 61 2 27.5 2580 0.0754 781
1 x 300.0 61 2.1 30 3200 0.0601 902
1 x 400.0 61 2.4 34 4200 0.047 1085
1 x 500.0 61 2.6 37.5 5180 0.0366 1253
1 x 630.0 91 2.8 40.5 6425 0.0283 1454
1 x 800.0 91 3.1 51.2 9469 0.0221 945
1 x 1000.0 91 3.3 56.7 11585 0.0176 1063

 

 

  • TWO / THREE / FOUR CORE COPPER CONDUCTOR XLPE INSULATED & PVC SHEATHED G.I. STRIP ARMOURED CABLES ACCORDING TO IS : 7098/PT. 1/1988
 Size Stranding(Minimum No. of Strands) Nominal Thickness of Insulation(mm) Nominal Overall Diameter(mm) Approx. Weight (Kg/Km) Max DC Resistance at 20 Degree C Current rating (Amp)
SQ.MM
2 Core 3 Core 4 Core 2 Core 3 Core 4 Core 2 Core 3 Core 4 Core 2 Core 3 Core 4 Core
16 6 0.7 18.5 20 825 1050 1.15 100 100
25 6 0.9 18.5 20.5 23 910 1235 1520 0.727 149 127 127
35 6 0.9 20 23 25 1025 1550 1915 0.524 185 158 158
50 6 1 22.5 25.5 28 1435 2020 2510 0.387 225 192 192
70 12 1.1 25.5 30 33 1910 2720 3430 0.268 289 246 246
95 15 1.1 28 33.5 36.5 2475 3500 4450 0.193 352 298 298
120 15 1.2 30 35.5 40.5 2985 4320 5575 0.153 410 346 346
150 15 1.4 34 40.5 45.5 3600 5280 6710 0.124 381 399 399
185 30 1.6 37 44.5 50.5 4490 6385 8225 0.0991 438 456 456
240 30 1.7 41 49 56.5 5575 8150 10345 0.0754 512 538 538
300 30 1.8 62.06 66.58 74 7541 10519 13626 0.0601 581 480 480
400 30 2 70 75.2 83.74 9666 13595 17672 0.047 662 546 546

NOTE : 2C x 10 & 3C X 10 SQ.MM size -As pER IS :7098 Strip Armouring is not Applicable

 

  • THREE AND HALF CORE XLPE INSULATED & PVC SHEATHER G.I. STRIP  ARMOURED CABLES ACCORDING TO IS : 7098/PT. 1/1988
Core Size Stranding(Minimum No. of Strands) Nominal Thickness of Insulation(mm) Nominal Overall Diameter(mm) Approx. Weight (Kg/Km) Max DC Resistance at 20 Degree C Current Rating(amp)
SQ.MM
M N M N M N
3.5 X 25 6 6 0.9 0.7 23 1410 0.727 1.15 108
3.5 X 35 6 6 0.9 0.7 25 1725 0.524 1.15 132
3.5 X 50 6 6 1 0.9 28 2325 0.387 0.727 162
3.5 X 70 12 6 1.1 0.9 32 3110 0.268 0.524 198
3.5 X 95 15 6 1.1 1 36 8975 0.193 0.387 240
3.5 X 120 18 12 1.2 1.1 40 4960 0.153 0.268 276
3.5 X 150 18 12 1.4 1.1 44 5870 0.124 0.268 318
3.5 X 185 30 15 1.6 1.1 50 7275 0.0991 0.193 366
3.5 X 240 30 18 1.7 1.2 55 9300 0.0754 0.153 426
3.5 X 300 30 15 1.8 1.4 61 11698 0.0601 0.125 480
3.5 X 400 30 30 2 1.6 67 15005 0.047 0.0991 546

 

 

  • TABLE – 4 MULTICORE COPPER CONDUCTOR XLPE INSULATED & PVC SHEATHER G.I. STRIP  ARMOURED CABLES ACCORDING TO IS : 7098/PT. 1/1988
Core Size Stranding(Minimum No. of Strands) Nominal Thickness of Insulation(mm) Cable Diameter Approx. Weight (Kg/Km) Max DC Resistance at 20 Degree C Current Rating(amp)
SQ.MM
16 X 1.5 1 0.7 19 750 12.1 14
19 X 1.5 1 0.7 20 815 12.1 13
21 X 1.5 1 0.7 21 900 12.1 12
24 X 1.5 1 0.7 23 1000 12.1 12
27 X 1.5 1 0.7 23.5 1050 12.1 11
30 X 1.5 1 0.7 24 1125 12.1 11
33 X 1.5 1 0.7 25 1225 12.1 10
37 X 1.5 1 0.7 26 1325 12.1 10
44 X 1.5 1 0.7 28.5 1500 12.1 9
52 X 1.5 1 0.7 30.5 1700 12.1 9
61 X 1.5 1 0.7 32 1950 12.1 8

 

  • TABLE – 5  MULTICORE COPPER CONDUCTOR XLPE INSULATED & PVC SHEATHER G.I. STRIP  ARMOURED CABLES ACCORDING TO IS : 7098/PT. 1/1988
Core Size Stranding(Minimum No. of Strands) Nominal Thickness of Insulation(mm) Nominal Overall Diameter(mm) Approx. Weight (Kg/Km) Max DC Resistance at 20 Degree C Current Rating(amp)
SQ.MM
10 X 2.5 1 0.7 19 700 7.41 21
12 X 2.5 1 0.7 19.5 760 7.41 20
14 X 2.5 1 0.7 20 850 7.41 19
16 X 2.5 1 0.7 21.5 820 7.41 18
19 X 2.5 1 0.7 22.5 1025 7.41 17
21 X 2.5 1 0.7 23.5 1140 7.41 16
24 X 2.5 1 0.7 25.5 1250 7.41 16
27 X 2.5 1 0.7 26.5 1350 7.41 16
30 X 2.5 1 0.7 27.5 1550 7.41 14
33 X 2.5 1 0.7 28.5 1630 7.41 14
37 X 2.5 1 0.7 29.5 1710 7.41 13
44 X 2.5 1 0.7 33 2100 7.41 12
52 X 2.5 1 0.7 34.5 2350 7.41 12
61 X 2.5 1 0.7 36 2625 7.41 11